Monitoring voltage relay HRN-57

Serves to monitor voltage in a switchboard, protection of devices in 3-phase main

DESCRIPTION

  • Relay doesn’t monitor phase sequence.
  • Supply is done from monitored voltage.
  • Fixed T1(500ms) and adjustable T2 (0.1 – 10 s) delay to eliminate short voltage drops and peak.
  • In case supply voltage falls below 60 %Un (U off lower level) relay immediately switch OFF with no delay.
  • It is possible to set upper and lower level independently.
  • Monitoring voltage relay in two variants:

HRN-57: supply from all phases, means that relay is functional also in case of failure in one phase
HRN-57N: supply L1-N, means that relay monitors also failure of neutral wire, replacement for HRN-52

  • Faulty state is indicated by red LED and by breaking output relay contact.

TECHNICAL PARAMETERS

  • Monitored power voltage: 

HRN-57: 3 x 400 V 
HRN-57N: 3 x 400 V/ 230 V

  • Umax: 105 – 125% of monitored voltage.
  • Umin: 75 – 95% of monitored voltage.
  • Output contact: 1x changeover 8 A/250 V AC1 (AgNi, 2500 VA)

Downloads

Calendar

<
November 2019
>
  • Mo
  • Tu
  • We
  • Th
  • Fr
  • Sa
  • Su
  •  
  •  
  •  
  •  
  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30

Customer Centre

Reception

+420 800 100 671
elko@elkoep.com

Technical support

+420 573 514 242
support@elkoep.com